88

71.03982.03 - EN

INSTALLATION INSTRUCTIONS

26. CONNECTING THE EXTERNAL SENSOR

The wiring harness leaving the control board includes two RED wires fitted with faston covers. Connect the external sensor 
to these two wires.
With the external sensor connected, the “

kt

” curve (Graph 2) can be changed by pressing 

+/-

 

.

N.B.: In case of installation in an average living unit (good perimeter insulation and radiator systems), set the “

kt

” climate 

curve to “25”.

27. CONNECTING AN EXTERNAL STORAGE BOILER

Model 24 - 24FF

The DHW priority sensor NTC is supplied as an accessory.

CONNECTING THE STORAGE BOILER SENSOR

The boiler can be connected to an external storage boiler. Hydraulically connect the storage boiler as shown in fig. 14. 
Connect the DHW priority sensor NTC to terminals 5-6 on terminal block M2. The sensitive element of the NTC sensor must 
be inserted in the special well located on the storage boiler. Adjust DHW temperature (35 °C...60 °C) by pressing 

+/–

 

.

Figure 14

KEY

:

UB

  STORAGE BOILER

UR

 HEATER

V3V

  EXTERNAL THREE-WAY VALVE

M2

  CONNECTING TERMINAL 

BLOCK

SB

  DHW PRIORITY STORAGE 

BOILER SENSOR

MR

  HEATING FLOW

MB

  STORAGE BOILER FLOW

RR

  HEATING / STORAGE BOILER 

RETURN

IMPORTANT :

 Make sure that parameter 

F03 = 03

 (section 21).

TM

 = Flow temperature range

Te

 = External temperature

Graph 2

TM

Te

“kt” curves

1012_0501

CG_2085 / 1101_1701