Руководство пользователя для De Dietrich MS 24 MI FF :: Страница 85 из 332
Service-Instruction.ru
инструкции pdf и руководства пользователя читать онлайн
background image

85

71.03982.03 - EN

INSTALLATION INSTRUCTIONS

Description of parameters

Factory settings

24 MI FF

24 FF

24 MI

24

F01

Type of boiler

10

 = sealed chamber 

20

 = atmospheric chamber

10

10

20  

20

F02

Gas used

00

 = METHANE

01

 = LPG 

02

 = METHANE (WITH DIAPHRAGM)

02

F03

Hydraulic system

00

 = instantaneous appliance

03

 = appliance with external storage boiler

04

 = appliance for heating only

13

 = preheating (24h)

14

 = preheating (1h)

13

04

13

04

F04/ F05

Setting programmable relays 1 and 2 (See SERVICE instructions)

00

 = no associated function

00

F06

Maximum CH setpoint (°C)

00

 = 85°C - 

01

 = 45°C (function unavailable)

00

F07

DHW inlet priority configuration

00

01

00  

01

F08

CH max. output 

(0-100%)

100

F09

DHW max. output 

(0-100%)

100

F10

Min. heating output 

(0-100%)

00

F11

Delay prior to new ignition in CH mode 

(00-10 minutes) - 00=10 seconds

03

F12

Diagnostics (See SERVICE Instructions)

--      

F13-F14-F15

Factory settings

00

F16

Anti-legionella function 

(with F03=03)

00

 = disabled

55...67

 = enabled (setpoint °C) 

00

F17

CH pressure sensor selection

00

 = hydraulic pressure sensor 

01

 = hydraulic differential pressure sensor 

00

F18

Manufacture information 

00

21. PARAMETER SETTINGS

To set the boiler parameters, press (

–

  ) and (

–

 

) together and hold down for at least 6 seconds. When the function is 

activate, the “

F01

” appears on the display alternating with the value of the parameter shown.

Edit parameters

•  Press  (

+/–

 

) to scroll through the parameters;

•  Press  (

+/–

 

) to edit each parameter;

•  Press 

 (

)

, to save the changes. “

MEM

” appears on the display;

•  Press 

 

(

i

)

,

 to exit without saving. “

ESC

” appears on the display.

22. ADJUSTMENT AND SAFETY DEVICES

The boiler has been designed in full compliance with European reference standards and in particular is fitted with the 

following:

•  Air pressure switch (model 24 MI FF - 24 FF)

  This device only allows the burner to ignite if the exhaust flue duct is in perfect working order.

  In the event of one or more of the following faults:

•  flue terminal obstructed

•  venturi tubes obstructed

•  fan blocked

•  venturi tube connection - pressure switch tripped

the boiler remains on standby and error code E03 is displayed (see table in section 10).

•  Fumes thermostat (model 24 MI - 24)

  This device has a sensor positioned on the left section of the fumes hood and shuts off the gas flow to the main burner 

if the flue is obstructed and/or if there is no draught.

  In these conditions the boiler shuts down and displays error code E03 (section 10).

  After eliminating the problem, press button ( ), for at least 2 seconds to re-ignite immediately.

It is forbidden to disable this safety device