77

71.03982.03 - EN

INSTALLATION INSTRUCTIONS

16. INSTALLING THE FLUE AND AIR DUCTS

Model 24 MI FF - 24 FF 

The boiler is easy and flexible to install thanks to the ex-
tensive range of available accessories, as described below.
The boiler has been designed for connection to a vertical 
or horizontal coaxial flue-air duct. A splitting kit is also 
available if separate ducts are required.

Only accessories supplied by the manufacturer must 
be used for installation!

WARNING: To optimise operating safety, make sure 

the flue ducts are firmly fixed to the wall with suitable 

brackets.

Figure 6

0503_0905/CG1638

… COAXIAL FLUE-AIR DUCT (CONCENTRIC)

This type of duct is used to discharge exhaust fumes and draw combustion air both outside the building and if a LAS flue 
is fitted.
The 90° coaxial curve allows the boiler to be connected to a flue-air duct in any direction as it can be rotated by 360°. It 
can also be used as a supplementary curve combined with a coaxial duct or a 45° curve.

If fumes are discharged outside the building, the flue-air duct 
must protrude at least 18 mm from the wall to allow an alu-
minium weathering surround to be fitted and sealed to avoid 
water infiltrations.
Make sure there is a minimum upward slope towards the 
outside of 1 cm per metre of duct.

•

  

A 90° curve reduces total duct length by 1 metre.

•

  

A 45° curve reduces total duct length by 0.5 metres.

The first 90° curve is not considered when calculating the 

maximum available length.

Figure 7

0805_2901 / C

G_2073

Connector

Boiler model

Length (m)

Use of DIAPHRAGM 

on INLET LINE

A

24 MI FF

24 FF

0 ÷ 1

Yes

1 ÷ 4

No