SPECIFICATIONS
MODEL
5E500i
5E650i
5E650iUSB
5E850iUSB
5E1100iUSB
5E1500iUSB
5E2000iUSB
CAPACITY
VA/W
500VA/
300W
650VA/
360W
650VA/
360W
850VA/
480W
1100VA/
660W
1500VA/
900W
2000VA/
1200W
INPUT
Input voltage
range
170V-264V
170V-280V
OUTPUT
Output on
battery
230V
Voltage
Regulation
(Bat. Mode)
+/-10%
Frequency
50Hz or 60Hz
Frequency
Regulation
(Bat. Mode)
+/-1 Hz
Output
Waveform
Modified Sine wave
BATTERY
Battery Type
(1)12V
4.5Ah
(1)12V
7Ah
(1)12V 7Ah
(1)12V 9Ah
(2)12V 7Ah
(2)12V 9Ah
(2)12V 9Ah
Recharge
Time
6 hours to 90% after complete discharge
COMMUNICATION
USB
No
Yes
TRANSFER TIME
Typical
2-6ms typical, 10ms max.
4-8ms typical, 10ms max.
INDICATOR
AC Mode
Green LED lighting
Battery
Mode
Green LED Flashing
SURGE
SUPPRESSION
RJ-11
protection
No
Yes
AUDIBLE ALARM
Backup
Mode
Sounding every 10 seconds
Low Battery
Sounding every 1second
Overload
Sounding every 0.5 second
Battery
replace
Sounding every 2 seconds
Fault
Continuously sounding
PROTECTION
Full
Protection
Discharge, overcharge, and overload protection
PHYSICAL
Dimensions
H*W*D
148*100*288
180*133*330
WEIGHT
Net Weight
3.7Kg
4.6Kg
4.6Kg
5.1Kg
9.3Kg
10.5Kg
10.5Kg
ENVIRONMENT
Operating
Environment
0°C - 40°C
Noise Level
Less than 40dB
Less than 45dB
Altitude
The maximum operating altitude must not exceed 2000m
BACK UP TIME
For a 100W
load
7min
16min
16min
20min
30min
40min
45min
Contact:
Eaton Power Quality
110 Rue Blaise Pascal
Batiment A Inovallee Immeuble
38330 Montbonnot-Saint-Martin
France
www.eaton.eu/5E Eaton 5E 500/650/850/1100/1500/2000
Important safety instruction - Read before installing product Safety of persons ► The UPS has its own internal power source (the battery). Consequently, the power outlets may be energized even if the UPS is disconnected from the AC-power source. ► Dangerous voltage levels are present within the
Instruções de segurança importantes - Leia antes de instalar o produto Segurança de pessoas ► ► ► A UPS tem a sua própria fonte de energia interna (a bateria). Consequentemente, as tomadas de saída AC podem estar energizadas mesmo que a UPS esteja desligada da corrente eléctrica. Níveis perigosos
Меры безопасности – Прочитать перед монтажом изделия Безопасность персонала ► ► ИБП оснащен собственным источником питания (аккумуляторной батареей). Таким образом, на его выходах может присутствовать напряжение, даже когда ИБП отсоединен от источника переменного тока. Внутри ИБП может
QUICKSTART
SYSTEM DESCRIPTION 1. Power management port only on USB models 2. ON/OFF button Port de communication uniquement sur modèles USB Interrupteur Marche/Arrêt Puerto de comunicación sólo en los modelos USB Interruptor Marcha/Paro Porta de comunicacão somente nos modelos USB Botão Liga/Desliga Порт для
TROUBLE SHOOTING Symptom No LED display on the front panel. Possible Cause 1. Battery weak. 2. Battery defect. 3. Power switch is not pressed. Alarm buzzer beeps continuously when AC Overload of the UPS. supply is normal. When power failure, back-up time is 1. Overload of the UPS. shorten. 2.
SPECIFICATIONS MODEL CAPACITY VA/W INPUT Input voltage range 5E500i 500VA/ 300W 5E650i 650VA/ 360W 5E650iUSB 650VA/ 360W 5E850iUSB 850VA/ 480W 170V-264V 50Hz or 60Hz +/-1 Hz Output Waveform Modified Sine wave (1)12V 4.5Ah (1)12V 7Ah (1)12V 7Ah Recharge Time USB TRANSFER TIME Typical INDICATOR AC